When selecting a humidifier, it’s important to make sure
that it can achieve the maximum duty required. This is well understood, but an
area that’s sometimes overlooked is the minimum capacity of the humidifier and
the effect it can have on maintaining the desired humidity level in a theatre,
office or manufacturing space.
This problem does not exist with the Gibbons
humidification system, as we can turn the humidifier output down to
virtually zero when required. Some alternative adiabatic
humidifiers have a limit when it comes to lower levels of humidification
they can achieve, often having a turndown ratio of only around 4:1. This means
that a humidifier with a maximum capacity of 200 kg/h can only achieve a
minimum of 50 kg/h as shown on the graph below.
Where the humidification load is moderate, such as during
spring and autumn, there will be many times where the humidity demand is below
the minimum that alternative humidifiers can achieve. In the example above, any
demand level below 50 kg/h cannot be achieved.
Now suppose that the air volume were to be reduced to,
say, half the maximum on which the humidifier capacity was calculated. This
might be as a result of how the air system operates or it might be a permanent
energy-saving measure now or in the future. It follows that halving the air
volume would halve the demand on the humidifier, so instead of having a maximum
load of 200 kg/h, the maximum would be 100 kg/h.
The minimum capacity of the alternative humidifier
remains the same, so now the possible turndown of the humidifier is reduced to
only 2:1, which severely limits the potential humidity control. The performance
of the Gibbons
humidifier would not be affected by the reduction in air volume because we
can reduce output to virtually zero. For example, we have installed our system
in a concert hall where the air volume is reduced to 10% of its maximum before
a performance, and our humidifiers are still able to maintain the correct
humidity level.
Below is a graph showing the maximum and minimum
humidification requirement per month for a typical London building running
24/7. It can be seen that there are many occasions where the minimum conditions
are below 50 kg/h, which mostly occur during daytime. In these conditions, it
will not be possible to maintain the correct humidity levels in the space.
If the airflow were to be halved, it can be seen that
there are many more conditions where the humidifier would not be able to
maintain the desired level.
So, remember to check the minimum output from the
humidifier you’re considering. If in doubt, choose Gibbons!
To find out about the many other benefits of Gibbons’
adiabatic humidification system, call Steve Rix on 07966 423165 or email steve.rix@gibbonsgroup.co.uk.